S11 Oil Filled Hermetically Sealed Distribution Transformer
Performance Characteristics
●The no-load loss of this series transformer is reduced by about 30% on average compared with the S9 transformer.
●The low voltage winding with capacity in the range of 630~2000kVA adopts cylinder or spiral structure, high mechanical strength, balanced ampere-turns distribution, and anti-short circuit energy of the product
Good force.
●The body is added with a positioning structure, so that it does not cause displacement during transportation. At the same time, all fasteners are installed with fastening nuts to ensure that the product is in long-term operation
In the process of tight firmware is not loose, full of no core lifting requirements.
●The ripple tank is used in the transformer, the oil storage tank is removed, and the cover and the edge of the box are completely welded or fastened with a bolt, which prolongs the service life of the transformer oil.
●The surface of the product is sprayed with primer and top paint after oil removal, rust removal and phosphating treatment, which can meet the special needs of metallurgy, stonification system and wet and dirty areas
Please.
●Selected components, using a fully sealed transformer tank, according to the standard requirements installed pressure release valve, signal thermometer, gas relay, etc., to ensure the variable pressure
Device safe operation. This series of products have beautiful appearance, small volume, and can reduce the installation area, which is a maintenance-free high-quality product.
Executive Standard
●GB1094.1~2-2013 Power transformer
●GB1094.3,5-2003 Power transformer
●GB1094.4-2005 Power transformer
●Technical parameters and requirements of GB/T6451-2015 three-phase oil-immersed electric transformer
Model Number And Meaning
Model Number: S11-M-□/□
S | 11 | M | □ | □ |
Three phase oil immersed transformer | Performance level code | Sealed construction | Rated capacity(KVA) | Voltage level(KV) |
Technical parameter
Rated capacity (KVA) | Voltage combination | Connection group label | No-load loss (W) | Load loss (W) | Short circuit resistance (%) | No-load current (%) | Weight(Kg) | External dimensions(mm) | Gauge (mm) | ||||
High tension (KV) | Tapoff (%) | Low pressure (KV) | Body weight | Oil weight | Total weight | L×W×H | |||||||
30 | 6 6.3 10 10.5 11 | ±5% or ±2 ×2.5% | 0.4 0.415 0.422 0.433 | Yyn0 or Dyn11 | 100 | 600/630 | 4.0 | 2.1 | 200 | 65 | 325 | 700×555×870 | 400×400 |
50 | 130 | 870/910 | 2.0 | 230 | 100 | 420 | 820×660×935 | 400×400 | |||||
63 | 150 | 1040/1090 | 1.9 | 260 | 110 | 460 | 850×660×950 | 450×450 | |||||
80 | 180 | 1250/1310 | 1.8 | 300 | 120 | 540 | 870×665×970 | 500×500 | |||||
100 | 200 | 1500/1580 | 1.6 | 350 | 145 | 620 | 880×670×1010 | 500×500 | |||||
125 | 240 | 1800/1890 | 1.5 | 400 | 170 | 710 | 930×690×1040 | 500×500 | |||||
160 | 280 | 2200/2310 | 1.4 | 485 | 180 | 830 | 865×765×1050 | 550 ×550 | |||||
200 | 340 | 2600/2730 | 1.3 | 520 | 185 | 990 | 1200×770×1070 | 550×550 | |||||
250 | 400 | 3050/3200 | 1.2 | 640 | 190 | 1130 | 1270×830×1120 | 550×550 | |||||
315 | 480 | 3650/3830 | 1.1 | 750 | 230 | 1330 | 1420×960×1190 | 550×550 | |||||
400 | 570 | 4300/4520 | 1.0 | 900 | 260 | 1560 | 1420×960×1220 | 660×660 | |||||
500 | 680 | 5150/5410 | 1.0 | 1100 | 300 | 1800 | 1500×1010×1275 | 660×660 | |||||
630 | 810 | 6200 | 4.5 | 0.9 | 1250 | 380 | 2125 | 1650×1140×1350 | 660×660 | ||||
800 | 980 | 7500 | 0.8 | 1400 | 440 | 2490 | 1750×1200×1510 | 820×820 | |||||
1000 | 1150 | 10300 | 0.7 | 1720 | 500 | 2900 | 1780×1260×1550 | 820×820 | |||||
1250 | 1360 | 12000 | 0.6 | 1860 | 580 | 3580 | 1860×1300×1610 | 820×820 | |||||
1600 | 1640 | 14500 | 0.6 | 2280 | 730 | 4070 | 1940×1360×1660 | 820×820 | |||||
2000 | 1940 | 18300 | Please contact us for detailed data. | ||||||||||
2500 | 2290 | 21200 |
Note:
1. The load loss value below the slash in the table applies to the products of the Dyn11 connection group.
2. For the technical parameters of the larger capacity 10kV class distribution transformer, the external size and weight data, please consult our company.
3.Transformer with various voltage combination, short-circuit impedance and connection mode can be provided according to user needs.
4. The weight and external dimension data in the table are for reference only, and are subject to change without further notice.